Technical Features
Working Principle
Circuit Diagram
How to Select Meter Model Correctly
For Mass Flowrate of Saturated Steam
For Mass Flowrate of Superheated Steam
For Gas Volumetric Flowrate under Operating Condition
For Gas Volumetric Flowrate under Standard Condition
For Volumetric Flowrate of Liquid
Structure of Vortex Flowmeter
How to Select Right Installing Site
Installation in Pipe with Insulating Layer
Change Direction of Amplifier Box
Wiring for Meter with Frequency Output Signal
Wiring for Meter with Two Wires 4-20mA Output Signal
Wiring for RS-485 Communication
How to Select Pressure and Temperature Measuring Point
Preparation before Operation
Model Selection
Meter Specification
Dimension of Meter Outline
Dimension for Fixed Inserted Vortex Flowmeter & Installation
Dimension of Adjustable Inserted Meter & Installation (with Ball Valve)
Installation of Pressure Transmitter & Thermal Resistor Pt100
Production Standards
Precaution for Selection and Usage of Explosion Proof Vortex Flowmeter
KTLU Vortex Flowmeter
 
  Precaution for Intrinsical Safe Meter in Operation
 
This intrinsical safe meter is approved by National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation (NEPSI), according to National Standard GB3896.1/4-2000, mark of explosion proof is ExibIICT4, certificate No. GYB06179. It combined with safety barrier to make up an intrinsical safe explosion proof system, which can be used in relevant hazardous areas. You need to care of follows before installation:
a) There is grounding terminal in meter housing, you must ground the meter reliably;
b) This intrinsical safe meter must be combined with safety barrier which must be approved by Organization of Explosion Proof Inspection to make up intrinsical safe system;
c) The three cores shielded cable (core cross section is 0.5mm2 , with insulating sheath ) be used for connecting between meter to safety barrier, the shielded layer be single-end grounded in non-hazardous area. Cable layout should eliminate the electromagnetic interference as possible and make the cable distribution capacitance within 0.05F;
d) Ambient temperature range: -25 - +50≧. The relationship between temperature levels of explosion proof mark and inflame temperature as below:
Temperature Level T1 T2 T3 T4 T5 T6
Inflame Temperature +400≧ +280≧ +180≧ +120≧ +85≧ +70≧

e) The safety barrier should be installed in non-hazardous areas and operation should be according to the operation instruction;
f) Customer should not change the electric elements by himself;
g) Must obey the regulations of National Standard GB50058-92 while installation and maintenance.
Configuration of Intrinsical Safe System



Safety barrier is zener or insulated type, please connect vortex flowmeter, flow calculator and safety barrier according to barrier instruction.
  Precaution for Flameproof Meter in Operation
This flameproof flowmeter is approved by National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation (NEPSI), according to National Standard GB3896.1/4-2000, mark of flameproof is Exd II BT4, certificate No. GYB06239.
a) Avoid opening wiring box and inlet wire box of flameproof vortex flowmeter for daily maintenance. Cut off power before open. If open the flameproof housing, flameproof surface should be protected with no damage. Put flameproof surface upwards and can not touch the earth directly when check.
b) Non-flameproof meter and lamp fixture etc. are not allowed for maintenance on site. All tools should be flameproof.
c) Grounding terminal is available on housing. Meter should be grounded reliably while operation.

 