KVAF Variable Area Flowmeter
 
 How to Install Flowmeter
To ensure meter operation performance and measuring accuracy, please pay attention to:
* Metal Variable Area Flowmeter must be installed vertically which verticality keeps less than 2o, fluids flows from bottom to top;
* When install flowmeter on process pipeline, bypass pipe should be installed to handle with malfunction conveniently or not to affect production during flushing;
* To ensure meter accuracy, more than 5D straight pipe should be at upstream and 250mm straight pipe at downstream;
* Require to equip magnetic filter if ferromagnetic material contained in fluids;
* Require to equip filter between valve and straight pipe once solid impurity exists in measured medium;
* For gas measurement, pipe pressure should be not less than 5 times pressure loss of meter to ensure float working stably;
* When the fluid temperature is high over 220≧ or so low as easy to crystallize, it needs to take measures of thermal insulation protection; jacket type should be applied for heating or cooling;
* It is necessary that all standards of the pipe flange, fastener, sealing gasket should conform to the standard of meter flange to ensure meter operation normally;
* Generally speaking, the metal variable area flowmeter do not require maintenance after normal operation. Some meter defects always happened during commissioning due to some dirty material in the pipe to cause float be blocked, and the pointer of indicator is stopped fixedly. At this time, first close the valves on both sides of the flowmeter, then disassemble the upper flange of the flowmeter, move out the float to clean and then reassemble. Care that the flange nuts should be tightened up evenly and hold the gasket;
* The flange on the process pipeline must be coaxial and parallel to the flange of the meter. To avoid the pipe vibration, suggest supporting the pipe. Control valve should be installed at the downstream of the flowmeter;
* Because the meter transmits signal by magnetic coupling, therefore to ensure the meter performance, ferromagnetic matter should not exist around the meter 10m at least;
* Gas meter is calibrated under specified pressure. If the gas on outlet of the meter is exhausted out to atmosphere directly, it would produces pressure loss at the float, and causing the data distortion. Therefore, require to install an exhausting valve at the meter outlet under this condition;
* Pay attention to install meter with PTFE liner. PTFE will be distorted under uneven pressure, so flange nuts should not be tightened unevenly; for flowmeter with LCD display, ensure to avoid sun shining indicator directly during installation, or would ruduce life of LCD.
Table of Max. torque
 